L T N ®                                            600 VOLT

SMALL DIAMETER FLEXIBLE                                                           90° C  DRY

CONTROL CABLE                                                                            & 75° C  WET

 

SCOPE

  This specification covers multi- conductor UL listed Type TC cable consisting of stranded, uncoated annealed copper which is insulated with a flame retardant polymer and nylon jacket, cabled together with fillers, as required, utilizing a mylar tape wrap and jacketed overall with a black low temperature, flame resistant, VW-1 neoprene.  LTN cables conform to UL Type power and control tray cables and Articles 318, 340, 500, and 501 of the National Electrical Code.  Cables pass UL 1277, IEEE 383 70, 000 BTU and 210, 000 BTU « Cable Tray Propagation Test, » IEEE 1202 flame test and CSA FT4 flame test.  Cables are rated 600 volts, 90ºC dry and 75ºC wet.  UL file no. E60749. 

 

APPLICATIONS

 UL listed and OSHA acceptable.  Recognized for use in Class 1 or 2, Division 2 hazardous locations.  To be used with messenger supported    

trays, raceways, troughs, channels, ducts, conduit, and for direct burial.  Recommended for wet or dry locations and outdoor in cable trays where a sunlight resistant rating is required.  Designed for control, power, lighting, telemetering, signal, relay traffic control, whereever flexible, small diameter cable is required such as cranes, hoists, and robotics.  Cables can be flexed at      -40ºC.

 

CONSTRUCTION

 Conductors :  Bare, soft annealed copper per ASTM B-3.

Insulation :  Each conductor is concentrically insulated with a 15 mil wall of high dielectric flame retardant polymer with 5 mil wall of clear polyamide (nylon) jacket extruded over primary insulation and conforming to UL requirements.

 Cabling :  The applicable number of conductors are cabled together with fillers as necessary with a suitable lay.  A clear mylar tape is helically applied over the core. 

Overall Jacket :

 Gas/vapor-tight heavy duty, flame and oil resistant neoprene (black).

UL-1277 table 10.1   

ICEA S-68-516 part 4 paragraph 4.4.3, Thickness : specified herein .

Colour coding :

 ICEA Method      1 Table K-2, except colours and numbers are printed on solid base colours for easy identification.  (See table 3 in « Colour Code» section page 38). 

 

Cable identification :

   Ink print on one side of jacket.  « LTN (size) AWG Type TC 90ºC wet, sun resistant, 600 volts Dir. Bur. (UL)-- --FT4.»        

Ink print on other side of jacket.

« (number of conductors and sequential footage )».

 

CONSTRUCTION OPTIONS

 Consult factory for cable speci- fications with alternative stranding and/or appropriate shields (aluminum/polyester tape, tinned- copper braid).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

                                                                                                                                                                                                                                                                  OSHA ACCEPTABLE.

 

CONDUCTOR DATA

 

STRANDS

PVC

NYLON

APPROX.

SIZE

NO./O.D.

INSUL.

ARMOR

O.D.

(AWG)

(INCHES)

(INCHES)

(INCHES)

(INCHES)

         

18

19/0.010

0.015

0.004

0.088

16

19/0.0117

0.015

0.004

0.100

14

19/0.0147

0.015

0.004

0.118

12

19/0.0185

0.015

0.004

0.141

         

 

 

CABLE DATA

18 AWG

16 AWG

14 AWG

12 AWG

No.

Overall

Approx.

Approx.

Overall

Approx.

Approx.

Overall

Approx.

Approx.

Overall

Approx.

Approx.

of

jacket

outside

weight

jacket

outside

weight

jacket

outside

weight

jacket

outside

weight

conds.

thickness

diameter

1000 ft.

thickness

diameter

1000 ft.

thickness

diameter

1000 ft.

thickness

diameter

1000 ft.

(mils)

(inches)

(pounds)

(mils)

(inches)

(pounds)

(mils)

(inches)

(pounds)

(mils)

(inches)

(pounds)

                         

2

45

0.280

55

45

0.295

59

45

0.320

67

45

0.360

109

3

45

0.290

61

45

0.310

79

45

0.340

76

45

0.380

172

4

45

0.315

73

45

0.335

88

45

0.370

112

45

0.415

178

5

45

0.340

81

45

0.365

94

45

0.400

126

45

0.455

210

6

45

0.370

90

45

0.395

109

45

0.435

148

45

0.495

223

7

45

0.400

106

45

0.425

124

45

0.470

161

60

0.565

231

8

45

0.425

117

45

0.460

142

45

0.505

192

60

0.605

297

9

45

0.455

128

45

0.490

157

60

0.565

232

60

0.640

363

10

45

0.480

142

45

0.505

165

60

0.595

244

60

0.670

379

11

45

0.505

149

45

0.515

189

60

0.630

249

60

0.710

391

12

45

0.470

154

45

0.500

189

60

0.590

256

60

0.670

410

13

45

0.485

163

60

0.550

217

60

0.610

303

60

0.695

423

14

45

0.500

182

60

0.570

238

60

0.630

317

60

0.715

468

15

45

0.515

197

60

0.580

245

60

0.645

326

60

0.735

499

16

60

0.560

210

60

0.595

257

60

0.660

353

60

0.755

526

17

60

0.575

219

60

0.615

262

60

0.680

377

60

0.780

533

18

60

0.585

227

60

0.625

277

60

0.695

389

60

0.795

556

19

60

0.595

257

60

0.640

338

60

0.710

404

60

0.810

589

21

60

0.625

278

60

0.665

351

60

0.745

444

80

0.890

638

25

60

0.660

363

60

0.715

375

60

0.805

524

80

0.960

794

30

60

0.715

363

80

0.765

461

80

0.895

639

80

1.025

920

37

60

0.780

431

80

0.870

579

80

0.975

758

80

1.115

1227

                         

           